Product images are for illustration purposes only.
Powertank Integrated UV System – For Fixed Speed Units
£720.00 inc. VAT
Integrated UV disinfection system – For use with Fixed Speed Powertank
PERFORMANCE RANGE
Recommended for flow rates of 36 lpm (8 gpm) Maximum Operating Pressure: 6 bar
Next Working Day Delivery (UK Mainland Only)
Price Match Promise | Find Out More
- Description
- Product Data
- Performance Data
- Downloads
- Reviews (1)
Description
Powertank Integrated UV System – For Fixed Speed Units
INSTALLATION & USE
UV systems deactivate chlorine-resistant parasites such as Cryptosporidium and Giardia, and harmful bacteria like Legionella & E.Coli which may be present in some incoming water supplies.
STAGE 1: FINE SEDIMENT REMOVAL
Stage 1 is a 5-micron sediment filter cartridge with antimicrobial protection provided by a silver-based antimicrobial agent included in the plastic matrix with a specific technology. The filter housing also has antimicrobial abilities to prevent the build-up of bacteria and algae within the housing.
STAGE 2: ULTRA VIOLET DISINFECTION UNIT
Stage 2 is a Viqua UV disinfection system for the purposes of inactivation of bacteria and viruses in the incoming water supply. This UV system has an integral countdown timer to indicate when the UV lamp needs to be replaced. UV lamps degrade over time and must be replaced every 12 months.
BENEFITS TO UV DISINFECTION
- Equipped to inactivate chlorine-resistant parasites such as Cryptosporidium and Giardia, harmful bacteria like E.Coli, and viruses not visible to the naked eye.
- Specially designed and tested Sterilume™-EX lamps provide consistent and reliable ultraviolet output over the entire life of the lamp (9000 hours) to ensure continuous purification. Always use Viqua genuine replacement lamps and sleeves.
- The system is simple to maintain and service allowing for easy lamp replacement.
- Built with a durable stainless steel chamber to prolong life and eliminate ultraviolet light degradation.
- The controller visually displays the remaining lamp life and will go into alarm if the lamp fails. Monitored systems are equipped with a UV sensor which provides a continuous readout of UV intensity.
- The controller has a sealed case to prevent damage from accidental water intrusion and is fully CSA and CE compliant.
- Monitored systems allow for the installation of an optional solenoid valve which will stop the flow of water through the chamber should the UV performance fall below a safe level.
CONSTRUCTION
Connection Size: 1″ BSP
Power Consumption: 35W
PERFORMANCE RANGE
Flow Rates: 8 GMP (36 lpm)
Maximum Operating Pressure: 6 Bar
Ambient Water Temperature: 2-40°C (36-104°F)
*Max Flow Rate @ 16mj/cm2: 3.6m3/hr
*Max Flow rate @ 30mj/cm2: 2.0m3/hr
Additional information
Weight | 16 kg |
---|---|
Dimensions | Length: 180 mm Width: 480 mm Height: 600 mm |
Performance Data
Downloads
1 review for Powertank Integrated UV System – For Fixed Speed Units
Add a review
You must be logged in to post a review.
Gavin H. (verified owner) –
Verified review - view original